INTRODUCTION:
A synchronous machine rotates at a constant speed in the steady state. Unlike induction machine the rotating air gap field and the rotor in the synchronous machine rotate at the same speed called the synchronous speed. A synchronous machine can operate as both motor and generator. They are used primarily as electrical power generators. They are usually large machines generating electrical power at hydro, nuclear or thermal power stations. Synchronous generators with power rating of several hundred MVAs are quite common in generating stations. Synchronous generators are the primary energy conversion devices of the world’s electrical power systems today. Because the rotor speed is proportional to the frequency of excitation, synchronous motors can be used in situations where constant speed drive is required.
In industry, synchronous motors are used mainly where constant speed is desired. In industrial drivers, therefore synchronous motors are not as widely used as induction or dc motors a linear version of the synchronous motor (LSM) is being considered for high speed transportation systems of the future.
An important feature of the synchronous motor is that it can drop either lagging or leading reactive current from the ac supply systems. A synchronous machine is a doubly excited machine. Its rotor poles are excited by a dc current and its starter buildings are connected to the ac supply. The air gap flux is therefore the resultant of the fluxes due to both rotor current and stator current. In a synchronous motor if the rotor field winding provides just the necessary excitation , the stator will draw no reactive current; that is the motor will operate at a unity power factor. If the rotor excitation current is decreased, lagging reactive current will be drawn from the ac source to aid magnetization by tr rotor field current and the machine will operate at a lagging power factor. If the rotor field current is increased leading reactive current will be drawn from the ac source to oppose magnetization by the rotor field current and the machine will operate at a leading power factor. Thus by changing the field current the power factor of the synchronous motor can be controlled. If the motor is not loaded but is simply floating on the ac supply system it will thus behave as a variable inductor or capacitor as its rotor field current is changed. A synchronous machine with no load is called a synchronous condenser. It may be used in power transmission systems to regulate line voltage. In industry synchronous motors are sometimes used with other induction motors and operated in an over-excited mode so that they draw leading current to compensate the lagging current drawn by the induction motors, thereby improving the overall plant power factor.
The field excitation of a synchronous machine may be provided by means of permanent magnets, which eliminate the need for a DC source for excitation. This can not only save energy for magnetic excitation but also dramatically simplify the machine structures, which is especially favorable for small synchronous machines, since this offers more flexibility on machine topologies. The diagram below illustrates the cross sections of two permanent magnet synchronous machines

SYNCHRONOUS MACHINE STRUCTURES
Stator and Rotor
The armature winding of a conventional synchronous machine is almost invariably on the stator and is usually a three phase winding. The field winding is usually on the rotor and excited by dc current, or permanent magnets. The dc power supply required for excitation usually is supplied through a dc generator known as exciter, which is often mounted on the same shaft as the synchronous machine. Various excitation systems using ac exciter and solid state rectifiers are used with large turbine generators.
There are two types of rotor structures: round or cylindrical rotor and salient pole rotor as illustrated schematically in the diagram below. Generally, round rotor structure is used for high speed synchronous machines, such as steam turbine generators, while salient pole structure is used for low speed applications, such as hydroelectric generators. The pictures below show the stator and rotor of a hydroelectric generator and the rotor of a turbine generator. EXCITATION SYSTEMS IN SYNCHRONOUS MACHINE
The basic function of the excitation system is to provide d.c. current to the synchronous machine field winding. It also performs protective and control functions essential to the satisfactory performance of the power system by controlling the field voltage an thereby the field current. The control functions include the control of voltage and reactive power flow, and the enhancement of system stability. The protective functions ensure that the capability limits of the synchronous machine, excitation system and other equipment are not exceeded.
Arrangement of and Requirements for an Excitation System.
The direct current required to energize the field winding of a synchronous machine is taken from what is known as an exciter. Most frequently, this is a d.c. generator whose shaft is mechanically coupled to that of the associated synchronous machine.
Apart from the main exciter, the system contains a pilot ( or auxiliary) exciter to energise the field winding of the separately excited main exciter, adjusting rheostats, contactors, remote control facilities, automatic voltage regulators, and some other items.
(1) Field current control. In large synchronous machines , te d.c. field current , If, runs into hundreds or even thousands of amperes. Therefore, it would be wasteful of power to adjust it with a rheostat connected in the field (armature) circuit of the exciter. The losses in the rheostat would markedly reduce the efficiency of the synchronous machine.
The field current is therefore adjusted solely by varying the exciter field voltage, Vf , because the field current varies
Elements of an Excitation System
1) Exciter : Provides dc power to the synchronous machine field winding, constituting the power stage of the excitation system.
2) Regulator : Processes and amplifies the input control signals to a level and form appropriate for control of the exciter. This includes both regulating and excitation system stabilizing functions.
3) Terminal voltage transducer and load compensator : Senses generator terminal voltage, rectifies and filters it to dc quantity, and compares it with a reference which represents the desired terminal voltage. In addition, load (or line-drop, or reactive) compensation may be provided, if it is desired to hold constant voltage at some point electrically remote from the generator terminal ( for example, part way through the step-up transformer).
4) Power system stabilizer : Provides an additional input signal to the regulator to damp power system oscillations. Some commonly used input signals are rotor speed deviation, accelerating power and frequency deviation.
5) Limiters and protective circuits : These inclue a wide array of control and protective functions which ensure that the capability limits of the exciter and synchronous generator are not exceeded. Some of the commonly used functions are the field-current limiter, maximum excitation limiter, terminal voltage limiter, volts-per0Herts regulator and protection, and underexcitation limiter. These arenormally distinct circuits and their output signals may be applied to the excitation system at various locations as a summing input or a gated input.

Types of Excitation Systems
DC excitation system: This is the traditional method. A DC generator mounted on the main shaft may be of either the shunt-wound or the separately-excited type. The output current is fed to the rotor of the synchronous machine through slip-rings.
• Static excitation system: Here, DC excitation can be obtained by means of a rectifier and a suitable AC supply. This method eliminates the commutation limits inherent in DC exciters. The rectifier unit has no moving parts, requires very little maintenance, and is immune to hazardous or dusty atmospheres.
• AC excitation system: The AC exciter is mounted on the main shaft. Its field is fed from a pilot exciter, whose field in turn is obtained from a permanent-magnet generator.
The AC exciter output voltage is rectified and fed to the field of the synchronous machine via slip-rings.
DC excitation system:
Source of excitation power: DC generators.
The system provides current to the rotor of the synchronous machine through the slip rings. The exciter may be driven by a motor or the shaft of the generator. It may be self-excited or separately excite. When separately excited, the exciter field is supplied by a pilot exciter comprising a permanent magnet generator.
AC excitation system:
Source of excitation power: Alternators (ac machines)
The ac output of the exciter is rectified by either controlled or non-controlled rectifiers to produce the direct needed for the generator field. The rectifiers may be stationary or rotating.
The different forms of AC excitation systems are:
1) Stationary rectifier systems: With stationary rectifiers, the dc output is fed to the field winding of the main generator through slip rings. When non-controlled rectifiers are used, the regulator controls the field of the ac exciter, which in turn controls the exciter output voltage.
2) Rotating Rectifier Systems: With rotating rectifiers, the need for slip rings and brushes is eliminated, and the dc output is directly fed to the main generator field. The armature of the ac exciter and the diode rectifiers rotate with the main generator field. A small ac pilot exciter, with a permanent magnet rotor rotates with the exciter armature and the diode rectifiers. The rectified output of the pilot excitor stator energises the stationary field of the ac exciter. The voltage regulator controls the ac exciter field, which in turn controls the field of the main generator.
Such a system is referred to as a Brushless Excitation System. It was developed to avoid problems with the use of brushes that were perceived to exist when supplying the high field currents of very large generators. However with well maintained brushes these problems did not actually develop. AC excitation systems with and without brushes have performed equally well. High initial-response performance of brushless excitation can be achieved by special design of the ac exciter and high voltage forcing of the exciter stationary field winding. These systems do not allow direct measurement of generator field current or voltage. Manual control of main generator voltage is provided by an adjustable dc input setting to the thyristor gating circuits.

Static Excitation Systems:
Components in these systems are static or stationary. Controlled or uncontrolled, static rectifiers supply the excitation current directly to the field of the main synchronous generator through slip rings. The supply of power to the rectifiers is from the main generator ( or the station auxiliary bus) through a transformer to step down the voltage to an appropriate level, or in some vases from auxiliary windings in the generator. The forms of static excitation systems:
1) Potential-source controlled-rectifier systems: The excitation power is supplied through a transformer from the generator terminals or the station auxiliary bus, and is regulated by a controlled rectifier. This type of excitation system is also commonly known as a bus-fed or transformer-fed static system. This system has a very small inherent time constant. The maximum exciter output voltage (ceiling voltage) is, however, dependent on the input ac voltage. Hence, during system fault conditions causing depressed generator terminal voltage, the available exciter ceiling voltage is reduced. This limitation of the excitation system is, to a large extent, offset by its virtually instantaneous response and high post-fault field-forcing capability. In addition, it is inexpensive and easily maintainable. For generators connected to large power systems such excitation systems perform satisfactorily. Compounding ancillaries, such as those described below, are not normally justified; they are likely important for generators feeding power directly into small industrial networks with slow fault-clearing.
2) Compound-source rectifier systems: The power to the excitation systems in this case is formed by utilizing the current as well as the voltage of the main generator. This may be achieved by means of a power potential transformer (PPT) and a saturable-current transformer (SCT). Alternatively the current and voltage sources may be combined by utilizing a single excitation transformer, referred to as a saturable-current potential transformer (SCPT). The regulator controls the exciter output through controlled saturation of the excitation transformer when the generator is not supplying the load, the armature current is zero and the potential source supplies the entire excitation power, under loaded conditions, part of the excitation power is derived from the generator current. During a system fault condition, with severely depressed generator terminal voltage, the current input enables the exciter to provide high field-forcing capability.
3) Compund-controlled rectifier excitation systems: This system utilizes controlled rectifiers in the exciter output circuits and the compounding of voltage and current-derived sources within the generator stator to provide excitation power. The result is a high initial-response static excitation system with full “fault-on” forcing capability.
Since the source of power to a static excitation system is the main generator, it is in effect self-excited. The generator cannot produce any voltage until there is some field current. It is therefore necessary to have another power source of power for a few seconds to initially provide the field current and energise the generator. This process of build-up of generator field flux is called field flashing. The usual field-flashing source is a station battery.

Recent Developments and Future Trends:
The advances in excitation control systems have been influenced by developments in solid-state electronics and the latest development has been the introduction of digital technology. Developments in analog-integrated circuitry have made it possible to easily implement complex control strategies. Thyristors continue to be used for the power stage. The control, protection and logic functions have been implemented digitally. Digital controls provide a cheaper and possibly more reliable alternative to analog circuitry. They have the added advantage of being more flexible allowing easy implementation of more complex control strategies, and interfacing with other generator control and protective functions.

Dynamic performance measures:
The effectiveness of an excitation system in enhancing power system stability is determined by some of its key characteristics. In this section, we identify and define performance measures which determine these characteristics and serve as a basis for evaluating and specifying the performance of the excitation control system. Following Figure shows the representation of the overall excitation control system in the classical form used for describing feedback control systems.

The performance of the excitation control system depends on the characteristics of excitation system. the generator. and the power system. Since the system is nonlinear. it is convenient to classify its dynamic performance into large-signal performance and small-signal performance. For large-signal performance, the nonlinearities are significant; for small-signal performance, the response is effectively linear. Large Signal Performance Measures: Large signal performance measures provides a means of assessing the excitation system performance for severe transients such as those encountered in the consideration of transient, mid-term and long-term stability of the power system. Such measures are based on the quantities defined below. To permit maximum flexibility in the design, manufacture, and application of excitation equipment, some of the performance measures are defined “under specified conditions”; these conditions may be specified as appropriate for the specific situation.
(a) Excitation system ceiling voltage: The maximum direct voltage that the excitation system is able to supply from its terminals under specified conditions. Ceiling voltage is indicative of the field-forcing capability of the excitation system; higher ceiling voltages tend to improve transient stability.
For potential source and compound source static excitation systems, whose supply depends on the generator voltage and current, the ceiling voltage is defined at specified supply voltage and current. For excitation systems with rotating exciters, the ceiling voltage is determined at rated speed.
(b) Excitation system ceiling current: The maximum direct current that the excitation system is able to supply from its terminals for a specified time. When prolonged disturbances are a concern, the ceiling current may be based on the excitation system thermal duty.
(c) Excitation system voltage time response: The excitation system output voltage expressed as a function of time under specified conditions.
(d) Excitation system voltage response time: The time in seconds for the excitation voltage to attain 95% of the difference between the ceiling voltage and rated load-field voltage under specified conditions.
The rated load field voltage is the generator field voltage under rated continuous load conditions with the field winding at (i) 75°C for windings designed to operate at rating with a temperature rise of 60°C or less; or (ii) 100°C for windings designed to operate at rating with a temperature rise greater than 60°C.
(e) High initial-response excitation system: An excitation system having a voltage response time of 0.1 seconds or less. It represents a high response and fast-acting system.
(f) Excitation system nominal response‘: The rate of increase of the excitation system output voltage determined from the excitation system voltage response curve, divided by the rated field voltage. This rate, if maintained constant, would develop the same voltage-time area as obtained from the actual curve over the first half-second interval (unless a different time interval is specified)
The nominal response is determined by initially operating the excitation system at the rated load field voltage (and field current) and then suddenly creating the three-phase terminal voltage input signal conditions necessary to drive the excitation system voltage to ceiling. It should include any delay time that may be present before the excitation system responds to the initiating disturbance. Excitation System Nominal Response.

Referring to above figure the excitation response is illustrated by line ac. This line is determined by establishing area acd equal to area abd:
Nominal response = (cd)/(ao)(oe) Where, oe = 0.5 s ao = rated load field voltage
The basis for considering a nominal time span of 0.5 s in the above definition is that, following a severe disturbance, the generator rotor angle swing normally peaks between 0.4 s a.nd 0.75 s. The excitation system must act within this time period to be effective in enhancing transient stability. Accordingly, 0.5 s was chosen for the definition time period of nominal response. In the past, the nominal response has been a well-established and useful criterion for evaluating the large-signal performance of excitation systems. With older and slower excitation systems, this was an acceptable performance measure, but it is not adequate to cover many of the modern excitation systems. In particular, it is not a good figure of merit for excitation systems supplied from the generator or the power system, due to the reduced capability of such systems during a system fault. For high initial-response excitation systems, the nominal response merely establishes the required ceiling voltage. The ceiling voltage and voltage response time are more meaningful parameters for such systems.
Small-Signal Performance Measures
Small-signal performance measures provide a means of evaluating the response of the closed-loop excitation control systems to incremental changes in system conditions. In addition, small-signal performance characteristics provide a convenient means for determining or verifying excitation system model parameters for system studies.
Small-signal performance may be expressed in terms of performance indices used in feedback control system theory:
• Indices associated with time response; and
• Indices associated with frequency response
The typical time response of a feedback control system to a step change in input is shown in figure below. The associated indices are rise time, overshoot, and settling time. Typical Time Response to step input.

Typical open-loop frequency response of an excitation control system with the generator open-circuited

A typical open-loop frequency response characteristic of an excitation control system with the generator open-circuited is shown in figure above. The performance indices associated with the open-loop frequency response are the low frequency gain G, crossover frequency , phase margin and gain margin . Larger values of G provide better steady-state voltage regulation, and larger crossover frequency indicates faster response. Larger values of phase margin and gain margin provide a more stable excitation control loop. (The reference here is to excitation control system stability and not power system synchronous stability.) In timing the voltage regulator, an improvement to one index will most likely be to the detriment of other indices. For example, an increase in regulator gain will shift the gain curve in figure above upward. This has the beneficial effect of increasing the low-frequency gain and crossover frequency, but has the undesirable effect of decreasing the gain and phase margins. In general, a phase margin of 40° or more and a gain margin of 6 dB or more are considered a good design practice for obtaining 8 Stable, non-oscillatory voltage regulator system.

Similar Documents

Free Essay

Importance of Socioloy to Communication

...ELECTRICAL MACHINES G.A.N BRIGHT REPORT PRESENTATION 1. Title 2. Aim 3. Apparatus/Equipments 4. Procedure/Method 5. Theory/Results 6. Safety Precaution 7. Conclusion N/B: Safety Precaution must be minimum of four PART 1 SYNCHRONOUS MACHINE 1.1 INTRODUCTION A synchronous machine is an a.c machine in which the rotor moves at a speed which bears a constant relationship to the frequency of currents, in the armature winding. A synchronous machine is one of the important type of electric machines. Large a.c networks operating at constant frequency of 50Hz rely almost exclusively on synchronous generators, also called the alternators, for the supply of electrical energy. Private, stand-by and peak load plants with diesel or gas-turbine prime movers also have synchronous generators. Synchronous motors provide constant speed industrial drives with the possibility of power factor correction. Synchronous machine are generally constructed in larger sizes. Small size alternators are not economical. The modern trend is to build alternators of very large size capable of generating 500MVA or even more. The synchronous motor is rarely built in small sizes owing to superior performance characteristics and economical construction of induction motors. 1.2 OPERATING PRINCIPLE The operating principle of a synchronous machine is fundamentally the same as that of a d.c machine, but, unlike the latter, in the synchronous machine...

Words: 5432 - Pages: 22

Premium Essay

Mr Chan Ur

...48550 Electrical Energy Technology Chapter 6. Synchronous Machines Topics to cover: 1) Introduction 2) Synchronous machine structures 3) Rotating magnetic field 4) Equivalent circuit model 5) Performance as a generator 6) Performance as a motor Introduction A synchronous machine is an ac rotating machine whose speed under steady state condition is proportional to the frequency of the current in its armature. The magnetic field created by the armature currents rotates at the same speed as that created by the field current on the rotor, which is rotating at the synchronous speed, and a steady torque results. Synchronous machines are commonly used as generators especially for large power systems, such as turbine generators and hydroelectric generators in the grid power supply. Because the rotor speed is proportional to the frequency of excitation, synchronous motors can be used in situations where constant speed drive is required. Since the reactive power generated by a synchronous machine can be adjusted by controlling the magnitude of the rotor field current, unloaded synchronous machines are also often installed in power systems solely for power factor correction or for control of reactive kVA flow. Such machines, known as synchronous condensers, may be more economical in the large sizes than static capacitors. With power electronic variable voltage variable frequency (VVVF) power supplies, synchronous motors, especially those with permanent magnet rotors, are widely used...

Words: 6536 - Pages: 27

Free Essay

Mr Ol

...Research Report 2005-27 Double Side Control of Wound Rotor Induction Machine for Wind Energy Application Employing Half Controlled Converters D. Panda, T. A. Lipo* Rockwell Automation Advanced Technology Lab, Richmond Heights, Ohio 44143, USA, dpanda@ieee. org *Department of Electrical and Computer Engineering University of Wisconsin, Madison, WI 53706, USA, lipo@engr.wisc.edu isconsin lectric achines & ower lectronics onsortium University of Wisconsin-Madison College of Engineering Wisconsin Power Electronics Research Center 2559D Engineering Hall 1415 Engineering Drive Madison WI 53706-1691 © 2005 Confidential Double side control of wound rotor induction machine for wind energy application employing half controlled converters Debiprasad Panda 1, Thomas .A.Lipo 2 Rockwell Automation Advanced Technology Lab, Richmond Heights, Ohio 44143, USA, dpanda@ieee.org 2 Department of Electrical and Computer Engineering University of Wisconsin, Madison, WI 53706, USA, lipo@engr.wisc.edu 1 Abstract – A double side converter fed wound rotor induction machine control for a wind energy application is proposed in this paper. In order to reduce the cost of a wind generator system, a new configuration using half controlled converters for both the stator and rotor circuit as well as for the line side is proposed. The proposed controller reduces the required KVA rating of both machine side and line side converters, improves the efficiency of the wind generator, helps operating...

Words: 5946 - Pages: 24

Free Essay

Analysis Details

...Analysis Detail For this analysis, the power system network to be studied is designed and simulated using the software, CYME 5.02 Power System Simulation Software. The system chosen for the study is that of a two machines system, involving two synchronous generators connected to a substation grid through circuit transmission lines. In order to gain much further comparison of the results, it is considered also the two different types of synchronous generators’ rotor types, salient-pole rotor and non-salient pole (round) type rotor. Transient stability studies are associated to the effects of faults on the synchronism of the generators. These disturbances may include faults on loss of load, loss of generation or loss of system components such as transformers or transmission lines. When fault is applied, the power generated from the nearby machine is reduced, producing speed differences during the time interval of the fault occurrence. Fig 1. Two machines system When the generator electrical load is suddenly increased, the electrical power exceeds the mechanical power input. This power deficiency is supplied by the kinetic energy stored in the rotating system. The reduction in kinetic energy resulted turbine speed to drop and as well as the frequency of the generator. This change of speed can be adjusted by a governor, which is an attachment to a machine for automatic control or limitation speed; it controls the energy through the prime mover to control its power. Governor...

Words: 641 - Pages: 3

Premium Essay

Induction Motors

...Introduction to Machines & Power Systems (EPM1076) Chapter 4c Synchronous Machines Objectives: In this chapter the following topics will be discussed.  Introduction to synchronous generator  Construction details  Principle of operation and emf equation  Equivalent circuit and voltage regulation  Short-circuit and open-circuit tests  Parallel operation  Synchronizing procedures Chapter IV EPM1076 2 Introduction to Synchronous Machines A synchronous machine is an ac rotating machine whose speed under steady state condition is proportional to the frequency of the current in its armature. The magnetic field created by the armature currents rotates at the same speed as that created by the field current on the rotor, which is rotating at the synchronous speed and a steady torque. Synchronous machines are commonly used as generators especially for large power systems, such as turbine generators and hydroelectric generators in the grid power supply. Because the rotor speed is proportional to the frequency of excitation, synchronous motors can be used in situations where constant speed drive is required. Chapter IV EPM1076 3 Chapter IV EPM1076 4 Angle in Electrical and Mechanical Unit -For 2 pole machine, when the rotor rotates for one revolution, the induce emf varies for one cycle. i.e. θ = θm, (refer to figure 2) -Where θ is the angle in electrical degrees or radians and θm is the mechanical angle. ...

Words: 2662 - Pages: 11

Free Essay

Gay Marriage

...State University of New York at Stony Brook Department of Electrical and Computer Engineering ESE218 Digital Systems Design Lab 9. Counter design. 1. Objectives - Design of the synchronous finite state machine (FSM) with D-flip-flops and multiplexers - Verification of the circuit behavior with a CAD tool 2. Problem description Design the synchronous 4-bit counter which outputs follow the predetermined repeated sequence of states. The sequence of states represents the sequence of decimal digits of your ID number with the following exceptions: (1) digits which appear more than ones have to be deleted; (2) digit 9 has to be added at the end of the sequence if your ID has no 9. For example, for ID number 105123456 the second 1 and 5 are deleted and 9 is added at the end resulting in sequence 10523469. In the binary form the sequence is shown in Figure 1. The initial state is not critical. State 9 should be decoded to generate special signal SYNC shown in denominator in Figure 1. In the prelab: the circuit behavior has to be verified in OrCAD. The maximum clock frequency has to be calculated using timing specs of the flip-flops and multiplexers (logical gates) from datasheet. In the experiment: first, the functionality of the counter has to be tested with a pushbutton that controls the clock and a 7-segment LED display connected to the outputs. Finally, the counter sequence should be demonstrated with the logic analyzer synchronized with SYNC signal, 4inputs of the logic analyzer...

Words: 1781 - Pages: 8

Premium Essay

Electrical Installation Standards

... APPROVED by Prikaz No 189 of the Minister of Power and Mineral Resources of the Republic of Kazakhstan, as of August 26, 2004.) REGULATIONS ON ELECTRICAL INSTALLATIONS OF THE REPUBLIC OF KAZAKHSTAN (PUE) Astana, 2003 TABLE OF CONTENTS SECTION 1: GENERAL REGULATIONS 10 CHAPTER 1.1: GENERAL 10 SCOPE, TERMS AND DEFINITIONS 10 GENERAL REGULATIONS FOR INSTALLATION OF ELECTRICAL EQUIPMENT 11 CONNECTION OF ELECTRICAL INSTALLATIONS TO THE POWER STATIONS 13 COMMISSIONING OF ELECTRICAL INSTALLATIONS 14 CHAPTER 1.2 POWER SUPPLY AND POWER SYSTEMS 14 SCOPE, DEFINITIONS 14 GENERAL REQUIREMENTS 14 CATEGORIES OF POWER CONSUMING DEVICES AND RELIABILITY OF POWER SUPPLY 15 VOLTAGE LEVELS AND CONTROLS, REACTIVE POWER COMPENSATION 16 CHAPTER 1.3 SELECTION OF CONDUCTORS: HEATING, CURRENT DENSITY AND CORONA DISCHARGE CONDITIONS 16 SCOPE 16 SELECTION OF CROSS-SECTION OF CONDUCTORS: HEATING 17 MAXUIMUM CONTINUOUS CURRENTS FOR WIRES, CORDS AND CABLES IN RUBBER OR PLASTIC INSULATION 18 MAXIMUM CONTINUOUS CURRENTS FOR CABLES IN IMPREGNATED PAPER INSULATION 22 MAXIMUM CONTINUOUS CURRENTS FOR BARE WIRES AND BUSES 29 SELECTING CROSS-SECTION OF CONDUCTOR PER THE ECONOMIC CURRENT DENSITY 33 CONDUCTOR...

Words: 177034 - Pages: 709

Premium Essay

Solar System

...a Stirling Engine Solar Power Generation System Using Simulink Mehdi Zareian Jahromi∗ , Mohammad Mehdi Hosseini Bioki† , and Roohollah Fadaeinedjad‡ , Member IEEE ∗† Electrical ‡ Electrical and Computer Engineering Department, Kerman Graduate University of Technology, Kerman,Iran. and Computer Engineering Department, Kerman Graduate University of Technology, Kerman,Iran. Telephone: +98-3426226517, Fax: +98-3426226618, Email: rfadaein@ieee.org ‡ International Center for Science, High Technology and Environmental Sciences, Kerman, Iran. could be especially useful in developing countries since they will run on any fuel, including biomass; or when incorporated in parabolic dish systems, they can use solar energy. Cogeneration is possible using the cooling water that maintains the cold sink, so heat-and-power systems for homes are provided. With higher efficiencies, their quiet vibration-free operation, very low emissions when burning natural gas, simplicity, and potentially high reliability could make the Stirling engines an attractive alternative in the near future [6]. Simulation and modeling can be used to evaluate the operation of the solar Stirling engine based power generation systems. Considerable research has been performed on the modeling and control of Stirling engine systems. Most of this research, however, has been done using mechanical and thermal models of Stirling engines that neglects the electrical parts of the system [5], [7], [8]. In this research, however,...

Words: 3882 - Pages: 16

Free Essay

Telecom Essay

...pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion. TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%. STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of...

Words: 785 - Pages: 4

Premium Essay

Renewable Energ

...honoured and pleased at the same time to work under the supervision of you, you spent a lot of time with us, at the time you definitely had lots of other important occupations. This work would have never been done without your assistance.Very thanking prof.Dr. Yasser Galal on his effort with us the past five years.Thanking engineers Noha Magdy and Ashraf Brdwyli to help us in the project. 3 ABSTRACT Wind energy is fast becoming the most preferable alternative to conventional sources of electric power. wind turbines are now coming up in almost all parts of the world. In the early days of development, wind turbines were designed to rotate at constant speed through pitch control or stall control. Wind electrical generation systems are the most cost-competitive of all the environmentally clean and safe renewable energy sources in the world. They are also competitive with fossil fuel generated power...

Words: 13966 - Pages: 56

Premium Essay

Switched Reluctance Motors Ad Their Uses

...permanent magnet assisted switched reluctance machine. Known generator adaptable for use in aircraft engines include flux switch generators, permanent magnet generators, lundell permanent magnet generators, wound rotor synchronous generators, Homopolar generators, hybrid homopolar generators, slave regulated generators and switched reluctance machines. Switched reluctance (SR) machines conventionally have multiple poles both stator and rotor; that is they are doubly salient. In switched reluctance machines, there is a concentrated winding on each of the stator poles, but no winding or magnets on the rotor. Each pair of diametrically opposed stator pole windings is connected in series or parallel to form an independent machine phase winding of the multiphase SR machine. Torque is produced by switching current in each machine phase winding in a predetermined sequence that is synchronized with angular position of the rotor, so that a magnetic force of attraction results between the rotor poles and stator poles. Current is switched off in each phase before the rotor poles rotate past the aligned position. The torque developed is independent of the direction of current flow, so that unidirectional current pulses synchronized with rotor movement can be applied to the stator pole winding by an inverter using unidirectional current switching elements, such as transistors or thyristors. For use as a generator, the current pulse in each machine phase winding are simply shifted so that current...

Words: 1928 - Pages: 8

Free Essay

Electric Machines

...Science 6.685 Electric Machines Class Notes 1: Electromagnetic Forces c 2003 James L. Kirtley Jr. September 5, 2005 1 Introduction Bearings Stator Stator Conductors Rotor Air Gap Rotor Conductors Shaft End Windings Figure 1: Form of Electric Machine This section of notes discusses some of the fundamental processes involved in electric machinery. In the section on energy conversion processes we examine the two major ways of estimating electromagnetic forces: those involving thermodynamic arguments (conservation of energy) and field methods (Maxwell’s Stress Tensor). But first it is appropriate to introduce the topic by describing a notional rotating electric machine. Electric machinery comes in many different types and a strikingly broad range of sizes, from those little machines that cause cell ’phones and pagers to vibrate (yes, those are rotating electric machines) to turbine generators with ratings upwards of a Gigawatt. Most of the machines with which we are familiar are rotating, but linear electric motors are widely used, from shuttle drives in weaving machines to equipment handling and amusement park rides. Currently under development are large linear induction machines to be used to launch aircraft. It is our purpose in this subject to develop an analytical basis for understanding how all of these different machines work. We start, however, with a picture of perhaps the most common of electric machines. 2 Electric Machine Description: Figure...

Words: 5431 - Pages: 22

Free Essay

Cognitive Science

... see in the night Opponent processing: Red/green: (L-M): differences between those 2 cones/ if miss L, then can’t tell red from green Blue/yellow: (s-s+m/2) Explicit: conscious Episodic/semantic Implicit: skill memory LTP: stronger synaptic connection Long term: grow more receptors on post synapse anatomical Short term: amount of neurons Turing machine Single vs double dissociation Single: one manipulation Double: two manipulations Visual angle Grandmother cell a lot of cells respond for Halle Berry Do not respond only to Halle Berry Math: impossibly large number of neurons Only 100 images do not necessarily show that those cells only respond to one concept Size constancy: If no depth cue/ with out size constancy; then same visual angle same proximal size and same perceived size. s Alternative: different difficulties of those 2 tasks Mediate by separate part of brain regions Color constancy Binding: different percepts What is intelligence? (Cartesian) Dualism, identity theory, functionalism The Turing test (and objections to it) Aunt Bertha machine Linear vs. exponential scaling Dualism: mind is nonphysical substance Identity theory: same mind state means the same brain state Problem of strict...

Words: 4004 - Pages: 17

Premium Essay

Speed Control Induction Motor

...Speed Control of Induction Motor using Fuzzy Logic Approach A PROJECT THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Bachelor of Technology In Electrical Engineering By Varuneet Varun (Roll 108EE011) G. Bhargavi (Roll 108EE026) Suneet Nayak (Roll 108EE044) Under Supervision of Prof. Kanungo Barada Mohanty Department of Electrical Engineering National Institute of Technology, Rourkela Rourkela- 769008, Odisha © 2011 - 2012 National Institute of Technology Rourkela Certificate This is to certify that the work contained in this thesis, titled “SPEED CONTROL OF INDUCTION MOTOR USING FUZZY LOGIC APPROACH” submitted by Varuneet Varun, G. Bhargavi and Suneet Nayak is an authentic work that has been carried out by them under my supervision and guidance in partial fulfillment for the requirement for the award of Bachelor of Technology Degree in Electrical Engineering at National Institute of Technology, Rourkela. To the best of my knowledge, the matter embodied in the thesis has not been submitted to any other University/ Institute for the award of any Degree or Diploma. Place: Rourkela Date: 11th May, 2012 Dr. Kanungo Barada Mohanty Associate Professor Department of Electrical Engineering National Institute of Technology Rourkela – 769008 i Acknowledgment We are grateful to The Department of Electrical Engineering for giving us the opportunity to carry out this project, which is an integral...

Words: 17434 - Pages: 70

Free Essay

Sub Sysnchronous Resonance

...A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy1, Member, IEEE, and Carlos Grande Moran2, Senior Member, IEEE Abstract: The paper presents a comprehensive approach for sub-synchronous resonance (SSR) screening analysis using a developed frequency scanning tool capable of handling power networks with hundreds of buses. PTI’s software packages like PSS/E and IPLAN programs were used for the development of the SSR tool. The frequency scanning technique scans for the sub-synchronous frequency range between 5 Hz to 59 Hz to determine the system driving point impedance (as a function of frequency) viewed from the neutral point of the generating unit under study. The proposed approach was applied to analyze the SSR phenomenon on several steam and gas driven turbine-generator plants in the northern part of the Western System Coordinating Council (WSCC) control area where several 500kV-transmission lines include series capacitor compensation. As a part of the study, credible contingencies that may lead to a network topology susceptible to SSR phenomenon are identified for proposed plants considered in the study. Key Words: Capacitor Compensated Transmission Lines, Sub-synchronous resonance. IEEE Sub-Synchronous Resonance Working Group report [4] presented the basic theory, problem definition, analytical tools, testing, and countermeasures for mitigating the SSR effects. The report also discussed some...

Words: 3927 - Pages: 16